EMU 32.x4 – the Allrounder with M-Bus, EIB KNX, LON or RS485

EMU 32.x4

EMU32.x4

The multifunctional 3-phase Energy Meter EMU32.x4 for direct connection (63A) or Current Transformer connection..
Price per kWh can be programmed by two buttons. Total costs are shown for tariff 1 and tariff 2.
The EMU32.x4 is equiped with a S0 Impulse output for Active Energy.

Technical Data EMU32.x4
 
Total
per phase L1/L2/L3
Tariff 1
Tariff 2
Active energy (kWh)
X
X
X
X
Price per kWh    
X
X
Total Cost    
X
X
Active power (W)
X
X
   
Current (A)
X
X
   
Voltage (V) L-N  
X
   

Nominal voltage Un 3 x 230/400V +/- 20%
3 x 127/220V +/- 20%
3 x 63 / 110V +/- 20%
Nominal (Maximum) Current: 5 (63) A
Measuring range: 0.025 to 63 A
Operating net frequency fn: 45 – 65 Hz
Meter burden: < 0.8 W / Phase
Accuracy class: 2 according IEC 1036
Operating Temperature range: -10 ºC to 50 ºC
Storage Temperature range: -40 ºC to +70 ºC
Terminal dimensions: 7 x 8 mm
Approval: METAS (Switzerland) and PTB (Germany)
Tariff control 230 VAC
Tariff 2 active: Voltage applied
Weight: ca. 320g
Installation: DIN BAR 35mm

In conformity with CE and IEC1036
Currrent and voltage circuits galvanically separated.


For current transformer connection:
Same data as for direct connection
CT connection /5A or /1A
CT ratio adjustable from 5/5A to 1275/5A in steps of 5A. >1275A ex factory
Measuring range: 0.005 bis 6A
Starting current <5 mA
Accuracy class 1 (+/- 1%)
 
Optional read-out interface:
M-Bus, EIB, RS485, IEC 61107
 
M-Bus read-out data:
Active energy Tariff1 (Wh)
Active energy Tariff 2 (Wh)
Reactive energy Tariff 1 (varh)
Reactive energy Tariff 2 (varh)
Instant. Current (A) per phase
Instant. Voltage (V) per phase
Instant. Active power (W) per phase
Instant. Reactive power (var) per phase
Instant. Power factor (Cos-Phi) per phase
Instant. Netfrequency (Hz)
15min Max. Active power Tarif 1 (W)
15min Max. Active power Tarif 2 (W)
Number of power failures
Operating hours
 
EIB KNX read-out data:
Active energy Tarif 1 (Wh)
Active energy Tarif 2 (Wh)
Instant. Active power Phase L1 (W)
Instant. Active power Phase L2 (W)
Instant. Active power Phase L3 (W)

Subject to change without notice

EMU Elektronik AG, Jöchlerweg 4, CH-6340 Baar, Phone +41 (0) 41 811 02 20, info@emuag.ch